3 – Universal Modbus Controller Configuration and Addressing
32
Location Syntax for Non-named Addresses
Addresses without names can be addressed directly using the format:
n:0xA [Format]
Table Types
Figure 10 Digital Output Control Strategy - Example 2
Calculated Value
Digital Output
Digital Variable
"Forced Value"
Digital Variable
"Force Enabled"
Digital Switch
A
B
SA
Part Description
n Table number. See “Table Types” on page 32 for table
descriptions and their number.
A Address within the table.
Format (Optional) Only used for Input and Holding register
tables (3 and 4). If a format is not specified, the format
defaults to IEEEFP. See “Data Formats” on page 33 for
more information.
Table Description Table Number Point Type Address Type
Digital Output (also
known as Coil)
1
0 Status Source/Destination
2
Digital Input 1 Status Source
Input Registers 3 Status/Analog/Accumulator Source
Holding Registers 4 Status/Analog/Accumulator Source/Destination
1. See “UMC800 Problems” on page 41 and “HC900 Problems” on page 43.