4 – Server and Station Tasks for Universal Modbus
40
Troubleshooting Universal Modbus Configuration Errors
Common Problems
Error message/problem Explanation/solution
You see the error in the server log file:
Error code 0106 (Device
Timeout)
The server has not received a response from the
controller.
You see the error in the server log file:
Error code 8102 (MODBUS
error 2 - illegal data
address)
You either specified an illegal address, or an
illegal number of addresses.
You see the error in the Station Message
Zone when you try to change the OP
parameter:
CONTROL - Illegal mode for
control of parameter
The point is in AUTO mode, or its equivalents
(AUTO-LSP, CASC, AUTO-RSP). You must
change the mode of the point to MAN or its
equivalents (MAN-LSP, MAN-RSP).
You see the error in the Quick Builder
output file:
Address is outside hardware
cross reference table
You have upgraded your database from a
previous server version and the there is not
enough room to store the controller addresses.
To rectify the problem, follow these steps:
1. Make a backup of \server\data.
2. At the command prompt, type:
sysbld -preserve -full.
3. Answer Y to the first two queries.
4. When presented with the ability to change
all sorts of database values, press <Enter>
until you see the following message:
There are 8192 addresses
per rtu. Enter required
number of addresses
5. Change the number of addresses per rtu
(controller) to 32766.
6. Keep pressing <Enter> until the sysbld
command terminates.